Wohner
Wohner Flexible Copper Busbar Plain Insulated 641A Model# 01323
Regular price
₱10,814.40
Tax included.
Part No.: 01323
flexible copper busbar, plain, insulated
8x 24 x 1
641 Ampere , length 2 m
flexible copper busbar, plain, insulated
8x 24 x 1
641 Ampere , length 2 m
Advantages of the product
The laminated Cu busbars considerably reduce the effort of connecting busbars. The bending devices required for solid copper busbars are unnecessary. The 2mm-thick insulation means that no additional covering is required.
| Details IEC | |
| Standards | |
| IEC 61439-1:2011 GB/T 7251.1 |
| Electrical data IEC | |
| Rated current (IEC): | 641 A |
| short-circuit withstandability: | see product description of the used busbar support |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 57.7 W.
(The power dissipation at full load would be 90.2 W.)
|
capacity depending on the permitted temperature rise of flexible copper busbar without impact of additional heat sources:
|
|
|
current at 30 K |
471 A |
| current at 40 K: | 562 A |
|
current at 50 K: |
641 A |
| current at 60 K: | 713 A |
| current at 70 K: | 779 A |
| notice the temperature stability of the insulation of 105 °C take conductors with required cross-section for connection to the products and devices (acc. to relevant standards or manufacturer instructions) |
|
| Details UL | |
| Standards | |
| UL 758 UL 67 |
| for UL feeder circuits >250V |
|
considering the permitted temperature rise at the concrete installation conditions the following capacity could be accepted by UL (file E197039 |
|
| capacity at 50 K: | 700 A |
| capacity at 65 K: | 810 A |
| Mechanical data | |
| L x W x D: | 2000 x 28 x 12 |
| weight: | 360 kg/100 |
| cross-section: | 192 mm² |
| Material properties | |
| Insulation: | temperature withstand up to 105 °C self-extinguishing, V0 according to UL 94 breakdown voltage 20 kV stretching 370 % |